57-13
Item No. 57-13










    MAIN DIMENSIONS AND STANDARD PARTICULARS

ANSI Class 57-13
Creepage Distance, mm 737
Dry Arcing Distance, mm 311
Cantilever Strength, kn 12.5
Low Frequency Flashover VoltageDry, kv 125
 Wet, kv 100
Critical Impulse Flashover VoltagePos., kv 210
 Neg., kv 260
Test Voltage to Ground, kv30
Maximum RIV at 1000KHZ, μv200
Net Weight, Each Approx., kg11.8




RECOMMENDED PRODUCTS